Contact Auxiliary MF/AX11 1NO+1NC for MCF3

Code: MF/AX11

Monitoring the device status - are its main contacts closed or open (regardless of the reasons that caused the opening).

 

Rated voltage Un, V
130V DC 230V AC 240V AC
Utilisation category
DC13 AC15 AC12
Rated current In, A
1 2 5
Rated operating voltage Un, V ~230
Rated frequency, f, Hz 50/60
Rated voltage of the insulation Ui, V 500
Rated pulse current output voltage Uimp, V 4000
Commutation wear resistance (electric/mechanical) 100 000/1 000 000
Protection degree IP20
Protection class ІІ
Cross-section of connecting conductors, mm² up to 2.5
Bolt tensioning torque, Nm 0.8
Connection side left
Altitude above sea level, m 2000
Operating temperature range, °C -25...+55
Storage temperature range, °C -40...+80
Warranty period of operation, years

5

Term of operation, years

not less than 15