Single phase voltage monitoring relay FRV11 230V,50/60HZ

Code: FRV11

The device is suitable for single phase submersible pumps. By monitoring undercurrent it avoid problems caused by dry running, cavitation etc.

 

  • Microcontroller based.
  • Supply voltage control.
  • Voltage measurement error.
  • Auto/reset.
  • LED indication for power supply and relay status.
  • Module DIN-rail mounting.

 

 

Standard EN/IEC 60730-1,
EN/IRC 60730-2-7
Supply voltage AC Un, V 220
Rated frequency, f, Hz 50/60
Voltage range, AC/V 150-275
U> setting value, V 225~275
U< setting value, V 165~215
Asymmetry setting 1%
Trip delay, s 0.1~10
Delay eror, s ±5%+0.1
Hysteresis ±3%
Current load, A <8/AC1
Number of poles 1 С/O
Contacts capacity 2A/AC15
Rated voltage of the insulation Ui, V 250
Protection class ІР20
Pollution degree 3
Commutation wear resistance
(electric/mechanical)
105/106 
Cross-section of connecting conductors, mm² 0.5...1
Bolt tensioning torque, Nm 0.5
DIN rail mounting yes
Altitude above sea level, m 2000
Operating temperature range, °C -5...+40
Storage temperature range, °C -10...+50