The temperature regulator is used to control heaters or floor heating system with a NTC sensor. The temperature regulating range can be adjusted by potentiometers.
| Standard | EN/IEC 60730-1, |
| Power supply terminals | А1, А2 |
| AC/DC supply voltage, V | 24-240 |
| Rated frequency, f, Hz | 50/60 |
| Measuring terminal | T1, T2 |
| Signal terminal | 21, 24 |
| Output terminal | 11, 14 |
| Temperature control range, °C | -25...+130 |
| Hysteresis, °C | +1...+30 |
| Control range, °C | -9...+9 |
| Step value setting, °C | 1 |
| Display | LCD |
| Output contact | 2NO |
| Current value AC1, A/V | 16/250 |
| V/A switching capacity AC1, W/DC | 4000, 300 |
| Degree of protection | ІР20 |
| Contamination level | 3 |
| Commutation wear resistance (electrical/mechanical) | 105/106 |
| Cross-section of connected wires, mm2 | 0.5 ... 2.5 |
| Bolt tightening torque, Nm | 0.5 |
| DIN rail mounting | TN 35 |
| Altitude above sea level, m | 2000 |
| Operating temperature range, °C | -5...+40 |
| Storage temperature, °C | -10...+50 |
| Temperature sensor | |
| Measuring element | NTC |
| Overall sensor size | Ø6x50 |
| Sensor material | steel |
| Cable length and size mm2/m | 2x0.3/2.5 |
| Cable material | silicon |
Додано у кошик