Residual current circuit breaker with over-current protection FAP10-A "C" 6А/0,1A 2P 10кА

Code: FAP10C06100A

FAP circuit breaker is recommended for use in civil engineering and administrative and commercial purposes. It should be used in rooms with a high level of moisture to protect equipment and avoid electric shock.

 

  • It combines the functions of circuit breakers and protective relays, while providing protection against short circuit currents, overload and earth leakage.
  • Protection of people from electric shock during direct or indirect contact with live parts.

 

CAD files
Residual current circuit breaker with over-current protection FAP10-A C 6A 100mA
Datasheet
Residual current circuit breaker with over-current protection FAP10-A "C" 6А/0,1A 2P 10кА

Standard IEC 61009
Number of poles 1P+N
Rated current In, A 6
Leakage current ІΔn, А 100
Rated voltage Un, V ~230
Time-current characteristics C
Limiting switching capacity Icu, A 10 000
Use category A
Commutation wear resistance (electric/mechanical)

6 000/20 000

Cross-section of connecting conductors, mm² up to 25
Differential protection type electromechanical
Rated voltage of the insulation Ui, V 500
Rated pulse current output voltage Uimp, V 4 000
Rated frequency, f, Hz 50/60
Selection class 3
Duration of the instant turning off, s ⩽0.1
Protection class IP20
Bolt tensioning torque, Nm 3.5
DIN rail mounting 35х7.5
Comb bus connection yes
Operating position any
Altitude above sea level, m 2 000
Operating temperature range, °C -25...+55
Storage temperature range, °C -25...+70