Automatic shutdown devices are recommended for using in civil construction as well as administrative and commercial purposes.
CAD files
Residual current circuit breaker with over-current protection FAP10-A B 6A 100mA
Datasheet
Residual current circuit breaker with over-current protection FAP10-A "B" 6А/0,1A 2P 10кА
| Standard | IEC 61009 |
| Number of poles | 1P+N |
| Rated current In, A | 6 |
| Leakage current ІΔn, А | 100 |
| Rated voltage Un, V | ~230 |
| Time-current characteristics | В |
| Limiting switching capacity Icu, A | 10 000 |
| Use category | A |
| Commutation wear resistance (electric/mechanical) | 6 000/20 000 |
| Cross-section of connecting conductors, mm² | up to 25 |
| Differential protection type | electromechanical |
| Rated voltage of the insulation Ui, V | 500 |
| Rated pulse current output voltage Uimp, V | 4 000 |
| Rated frequency, f, Hz | 50/60 |
| Selection class | 3 |
| Duration of the instant turning off, s | ⩽0.1 |
| Protection class | IP20 |
| Bolt tensioning torque, Nm | 3.5 |
| DIN rail mounting | 35х7.5 |
| Comb bus connection | yes |
| Operating position | any |
| Altitude above sea level, m | 2 000 |
| Operating temperature range, °C | -25...+55 |
| Storage temperature range, °C | -25...+70 |
| Warranty period of operation, years | 5 |
| Term of operation, years | not less than 15 |
Додано у кошик